Communication objects, 1 device profile area, Chapter7 communication objects lists – Hitachi SJ2-CO User Manual

Page 27

Advertising
background image

CHAPTER7 COMMUNICATION OBJECTS LISTS

23

7.Communication Objects

Communication Objects are grouped 3 areas.

Index

Profile Area

1000-1FFF

Communication Profile Area

2000-5FFF

Manufacturer Specific Profile Area(Inverter's parameter area)

6000-9FFF

Device Profile Area

7.1 Device Profile Area

Supported Communication Object by CANopen interface option ( ) =initial value

Index

Sub-Index

Object name

Data type

Note

6007h

abort_connection_option_code

INTEGER16

*

6040h

control word

UNSIGNED16

*

6041h

status word

UNSIGNED16

*

6042h

vl_target_velocity

INTEGER16

*

6043h

vl_velocity_demand

INTEGER16

*

6044h

vl_control_effort

INTEGER16

*

6046h

vl_velocity_min_max_amount

UNSIGNED32

0

Number of entries(=2)

INTEGER8

*

1

vl_velocity_min_amount

UNSIGNED16

*

2

vl_velocity_max_amount

UNSIGNED16

6048h

vl_velocity_acceleration

Ramp

0

Number of entries(=2)

INTEGER8

*

1

delta_speed

UNSIGNED16

*

2

delta_time

UNSIGNED32

*

6049h

vl_velocity_deceleration

Ramp

0

Number of entries(=2)

INTEGER8

*

1

delta_speed

UNSIGNED16

*

2

delta_time

UNSIGNED32

*

6060h

modes_of_operation

INTEGER8

*

6061h

modes_of_operation_display

INTEGER8

*

Note : This object cannot store to EEPROM.

Advertising