Heat & Glo • XLR-N-CE, XLR-PB-CE • 2198-900 Rev. L • 3/13

20

D. Mantel and Wall Projections

WARNING! Risk of Fire! Comply with all minimum clear-

ances to combustibles as specified. Framing or finishing

material closer than the minimums listed must be construct-

ed entirely of noncombustible materials (i.e., steel studs,

concrete board, etc).

Figure 5.3 Clearances To Combustible/Non-Combustible

Mantels Or Other Combustibles/Non-Combust-

ibles Above Appliance.

Mantels (Combustible/Non-Combustible)

Figure 5.4 Non-Combustible Mantel Leg or Wall Projections

(Acceptable on both sides of opening)

UNLIMITED

TOP VIEW

18 cm

8 cm

MINIMUM

36 cm

MIN.

30 cm

MAX.

1,3 cm

Thick Wall

Sheathing

MEASUREMENT

FROM TOP OF

FIREPLACE

OPENING

Note: For non-combustible fireplace finish material (marble,

stone, etc) specifications refer to Section 13.C.

Mantel Leg (Combustible/Non-Combustible)

8,90 cm

2,5 cm

AIR SPACE

NON-COMBUSTIBLE

BOARD SHIPPED

WITH APPLIANCE

2,5 cm

Figure 5.6 Non-Combustible Zone

Note: AIR SPACE denoted in Figure 5.6 is defined by the

nailing tabs and metal standoffs.

Note: Factory installed non-combustible board may only

be replaced with HHT product code

SUPERM-60 material

and must be fully replaced in its entirety.

Figure 5.5 Front Side Finishing Detail

2,5 cm

FRAMING

1,2 cm FACTORY-SUPPLIED

NON-COMBUSTIBLE BOARD

NAILING TAB