C. install the ceiling firestop – Heat & Glo Fireplace XLR-N-CE User Manual

Page 31

Advertising
background image

31

Heat & Glo • XLR-N-CE, XLR-PB-CE • 2198-900 Rev. L • 3/13

C. Install the Ceiling Firestop

A ceiling firestop

MUST be used between

floors and attics.

SLP pipe only - Frame opening 22,86 cm

x 22,86 cm whenever the vent penetrates

a ceiling/floor (see Figure 8.3).

• Frame the area with the same sized lumber

as used in ceiling/floor joist.

• The ceiling firestop may be installed above or

below the ceiling joists when installed with a

attic insulation shield. It must be under joists

between floors that are not insulated. Refer

to Figure 8.4.

• Secure with three fasteners on each side.
WARNING! Risk of Fire! DO NOT pack insu-

lation around the vent. Insulation must be kept

back from the pipe to prevent overheating.

Figure 8.3 Installing Ceiling Firestop

ATTIC ABOVE

A

PIPE
SLP

A

22,95 cm

A

Figure 8.4 Installing the Attic Shield

3 FASTENERS

PER SIDE

INSTALL ATTIC INSULATION SHIELDS

BEFORE OR AFTER INSTALLATION OF VENT SYSTEM

CEILING FIRESTOP

INSTALLED BELOW CEILING

CEILING FIRESTOP

INSTALLED ABOVE CEILING

Advertising
This manual is related to the following products: