14/38 Installation

Guide

SG Series 225 & 300 kVA

In case of parallel system, try to
place the UPS modules in
sequence of their numbers
(marked on the packing).

If the units are positioned “side
by side
”, the side panels must be
mounted on all units.

UPS 1

UPS

3-4-5-6-7-8

UPS 2

S

G

S

_225-300_RP

A

d

is

p

os

ition_G

E

_01US

Fig. 3.4.1-5 RPA system disposition






3.4.2 Battery

location


Batteries require a well-ventilated room with controlled temperature to obtain reliable
operation.

The Battery can be install immediately adjacent to the UPS (left or right side) or remotely
from the UPS.
If the Battery is installed remotely from the UPS, a wall mounted DC disconnect device must
be installed within line-of-site to both the UPS and the Battery.

The optimal room temperature for the Battery
is 68°F (20°C) to 77°F (25°C).

The life of valve-regulated batteries will be reduced by 50% for each additional 18°F (10°C)
that the Battery ambient temperature is above 77°F (25°C).

The Battery System associated with larger UPS is usually either rack mounted or installed in
multiple Battery Cabinets.

Installation and assembly must be made according to the local standards and Battery
System
manufacturer‘s recommendations.

The Battery Circuit Breaker or Battery Fuse Box must be mounted as near as possible to the
Battery.

Battery installation and connection must be performed by qualified
personnel only.

Read all safety instructions before proceeding with the installation.