GE 225 User Manual

Page 35

Advertising
background image

g

GE

OPM_SGS_ISG_M22_M30_0US_V011.doc

35/38

Installation

Guide

SG Series 225 & 300 kVA

4.1.1 Serial

Port

J3

Serial port J3 - RS-232 (sub D, female 9 pin) that allows:

Total remote management of the system using new generation software JUMP (Java
Universal Management Platform) for system protection and management of systems
using GE Industrial Systems UPS’s.
JUMP system is written in JAVA and supports virtually all platforms having JAVA
runtime environment version 1.1 or higher.

The serial port J3 - RS-232 is enabled on all the units of the parallel
system.

Serial port J3 connection to PC

Fig. 4.1.1-1 Serial port J3 connection to PC



4.1.2 Output potential free contacts

The interface board provide 6 voltage free relay contacts giving some UPS critical alarms
and operation mode.

These signals are available either on connector J2- (sub D, female 25 pin) or terminal
blocks X1.

The meaning of the alarms on the free contacts in standard configuration (default) is the
following:

X1 / 1, 2, 3

or J2 / 1, 2, 3

(NO, C, NC) Utility Failure

(def. Par. RL=1)

X1 / 4, 5, 6

or J2 / 4, 5, 6

(NO, C, NC) Load on Inverter

(def. Par. RL=3)

X1 / 7, 8, 9

or J2 / 7, 8, 9

(NO, C, NC) Stop Operations

(def. Par. RL=5)

X1 / 12, 13, 14

or J2 / 14, 15, 16

(NO, C, NC) Load on Utility

(def. Par. RL=2)

X1 / 15, 16, 17

or J2 / 17, 18, 19

(NO, C, NC) General Alarm

(def. Par. RL=4)

X1 / 18, 19, 20

or J2 / 20, 21, 22

(NO, C, NC) Acoustic Alarm

(def. Par. RL=6)

In case different alarms or operating status are required, they can be configured on the
same terminals via software from the control panel.

The configuration can be changed in parameters mode by a trained operator using the
appropriate password.

The programmable signals on X1 and J2 will be disabled with Q1 open, with
the exception of the signals for “16 - Manual Bypass ON”
and “26 - EPO”.

Advertising
This manual is related to the following products:

300