4 customer interface, 1 customer interface, X1 j2 j3 – GE 225 User Manual

Page 34: Jp3 xb

Advertising
background image

g

GE

OPM_SGS_ISG_M22_M30_0US_V011.doc

34/38

Installation

Guide

SG Series 225 & 300 kVA

4 CUSTOMER

INTERFACE

4.1 CUSTOMER

INTERFACE

Serial port J3 - RS 232 (sub D - female 9 pin)

Suitable for JUMP protocol

Pin 2: TX (out) Pin 3: RX (in) Pin 5: GND

J2 (subD-female 25p) – Output signals on voltage free contacts

J2/1, 2, 3

- NO,

C,

NC

- Utility

Failure

(def. Param. RL=1)

J2/4, 5, 6

- NO,

C,

NC

- Load on Inverter

(def. Param. RL=3)

J2/7, 8, 9

- NO,

C,

NC

- Stop Operation

(def. Param. RL=5)

J2/14, 15, 16

- NO,

C,

NC

- Load

on

Utility

(def.

Param.

RL=2)

J2/17, 18, 19

- NO,

C,

NC

- General Alarm

(def. Param. RL=4)

J2/20, 21, 22

- NO,

C,

NC

- Acoustic Alarm

(def. Param. RL=6)

Signals on terminals X1 and on connector J2 are in parallel
and therefore not separated galvanically from each other.

The programmable signals on X1 and J2 will be disabled with Q1 open, with
the exception of the signals for “16 - Manual Bypass ON”
and “26 - EPO”.

XB - Terminals for EPO connection

X2 / 1, 2 or J2 / 12, 25

NC

EPO (Emergency Power Off)

Note: to enable this function, remove cable short-circuiting XB / 2 – 3 and
the Jumper JP3 on P4 – Customer Interface.

X1 – Output signals on voltage free contacts - terminals

X1/1, 2, 3

- NO,

C,

NC

- Utility

Failure

(def. Param. RL=1)

X1/4, 5, 6

- NO,

C,

NC

- Load on Inverter

(def. Param. RL=3)

X1/7, 8, 9

- NO,

C,

NC

- Stop

Operation

(def.

Param.

RL=5)

X1/12, 13, 14

- NO,

C,

NC

- Load on Utility

(def. Param. RL=2)

X1/15, 16, 17

- NO,

C,

NC

- General

Alarm

(def.

Param.

RL=4)

X1/18, 19, 20

- NO,

C,

NC

- Acoustic

Alarm

(def.

Param.

RL=6)

Input contacts

X1/10, 21 or J2/10, 23

Programmable (default = RL1)

X1/11, 22

or J2/11, 24

Programmable / Generator ON (NO) (def. = RL2)

1

12
1

3

2

14

3

15

4

16

5

17

6

18

7

19

8

20

9

21

10

22

11

1

14

9

1

X1

J2

J3

SG

S_225

-300_Cust

ome

r i

nte

rfac

e_

01

J5

J4

XA

2

1

1

2

3

4

JP3

XB

1

2

3

4

Fig. 4.1-1 Customer interface

NO = normally open C = common NC = normally closed

The connectors J4 and J5 can be used for additional SNMP Card, Environmental Card (not available yet)
or an additional Customer Interface (installation only when the UPS is switched Off).
XA: terminals for 24VDC Auxiliary Power Supply connection. XB: terminals for EPO connection.

Programmable user relays

Programmable functions on contacts (X1 - J2)

On terminals X1 or J2 connector, six of the following 26
signals
can be selected from the display, entering with the
appropriate password.
0- No Information
1- Buzzer
2- General Alarm
3- Load on Utility
4- Stop Operation
5- Load on Inverter
6- Utility Failure
7- DC Over Voltage
8- Low Battery
9- Overload
10- Over Temperature
11- Inverter-Utility not syncr.
12- Bypass Locked
13- Bypass Utility Failure

14- Rectifier Utility Failure
15- Battery Discharge
16- Manual Bypass ON
17- Rectifier ON
18- Inverter ON
19- Boost Charge
20- Battery Earth Fault
21- Battery Fault
22- Relay Input 1
23- Relay Input 2
24- Relay Output ON
25- Relay Output OFF
26- EPO (Emergency

Power Off)

Some UPS functions can be activated with
parameters when an external Normally Open
contact is closed on:
X1-10, 21 / J2-10, 23 or X1-11, 22 / J2- 11, 24

Selectable functions by changing parameters
(password required) are:
0 - No function

1 - Inverter ON

2 - Inverter OFF

3 - Print All

4 - Status Relay

5 - Generator ON

6 - External Bypass ON
7 - External Battery Fuses, or External K3.

See Alarm 4104 - “Battery Fuses”.

Voltage free contacts: Max. DC / AC: 24V / 1.25A

IEC 950 (SELV circuit)
Min. Signal Level: 5VDC/50mA