1.3 Overview

The UPS provides two power paths between the utility source and the critical load.
Figure 1.1 shows the path for normal operation, with the load powered from the inverter.
Figure 1.2 shows the path for bypass operation, with the load supplied through the static
bypass line.
Figure 1.3 shows the path for battery operation, with the load supplied from the inverter.

A) Normal Operation.

FIGURE 1.1
Single Line Diagram - Normal Operation. Load powered by inverter














During normal operation, the path through the inverter is used to power the load.

Referring to Figure 1.1: Input AC power is converted to DC by the Converter. DC power is
utilized to charge the UPS battery and to provide power to the Inverter. The Inverter
converts the DC power to clean AC power to supply the critical load.

The conversion - inversion process eliminates any voltage transients or fluctuations
existing in the input power before it reaches the critical load.


* The AC Bypass Input circuit breaker (MCCB) for protection of the UPS and cables are field
supplied and field installed. (See WARNING 2 on page 1-2)

UPS Module

Power Flow

Not in Use

AC input

CB

FB

72B

52RS

CONVERTER

INVERTER

Output

52C

52RC

FI

FO

BATTERY

User
supplied

52CS

Maintenance
Bypass
Switch

50kVA, 80kVA:
External Battery

Static Transfer

Switch

CB

AC Bypass

Input