MITSUBISHI ELECTRIC 2033D SERIES UPS

MITSUBISHI
ELECTRIC

2033D SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

1-10

Description of Figures 1.4, 1.5, and 1.6:

1. External I/F Board (IOAU-05) : FOR SERVICE PERSONNEL ONLY (FIGURE 1.6):

- (3) External contact signal terminal
- (4) RS232C communication connector

2. Grounding

Bar

(E)

3. External Contact Signal Terminal Block - Terminal block to connect contact signal

input/output lines to and from the external devices. Refer to Figure 2.15 section 2.5 for
details.

4. RS232C Communication Connector - Refer to Figure 2.18 section 2.6 for details.
5. “INVERTER” START Switch - This switch is used to transfer the UPS from static bypass

to inverter during maintenance purposes. Transfers will lock-out if the bypass voltage is
more than +10%,-10% of nominal.
* Uninterrupted switching is made at the time of synchronous operation. Switching is impossible at

the time of asynchronous operation.

6. “INVERTER

STOP”

Switch - This switch is used to transfer the UPS from inverter to static

bypass during maintenance purposes. Do not operate it under normal operation. Transfers
will lock-out if the bypass voltage is more than +10%,-10% of nominal.
* Uninterrupted switching is made at the time of synchronous operation. Switching is impossible at

the time of asynchronous operation.

7. “FAULT RESET” Switch (FOR SERVICE PERSONNEL ONLY) - This switch resets

errors resulting from alarm conditions. (Do not operate this switch while inverter and
converter are in operation.)

8. Maintenance (Set) Button (FOR SERVICE PERSONNEL ONLY) - This switch sets the

UPS menu parameters.

9. “Test mode” Switch (FOR SERVICE PERSONNEL ONLY) - This switch changes system

operation to the test-mode. (This switch should not be operated by personnel other than
an Authorized Service Engineer).

10. “BOOT” Switch (FOR SERVICE PERSONNEL ONLY) - This switch boots the processor

in the main control circuit resulting from alarm conditions. (Do not operate this switch
while inverter and converter are in operation).