Mitsubishi electric – MITSUBISHI ELECTRIC 2033D SERIES UPS systems User Manual

Page 51

Advertising
background image

MITSUBISHI
ELECTRIC

2033D SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

6-4

MITSUBISHI ELECTRIC 2033D SERIES UPS

(Note 9)

Code

indication

Status message

Contents

Guidance

(Note 1)

Buzzer

(Note 2)
External

send-out

contact

(Note 3)

Failure

lamp

UA806

INVERTER OVERLOAD

> 100%

Overload exceeded 105% (Note 7)

WARNING:

DECREASE

LOAD

[2] Alarm -

UA809

INVERTER OVERLOAD

> 150%

Overload exceeded 150% (Note 7)

WARNING:

DECREASE

LOAD

[2] Alarm -

UA810 INVERTER

OVERLOAD

Instantaneous overload. (Output

voltage -30% for 2ms)

WARNING:

DECREASE

LOAD

[2] Alarm -

UA812

BYPASS VOLTAGE OUT

OF RANGE

Bypass voltage fell out of +/- 12%

range

CHECK BYPASS

INPUT

[3] Alarm -

UA813

BYPASS PHASE

ROTATION ERROR

Phase rotation is inverted when bypass

voltage is normal

CHECK BYPASS

INPUT

[2] Alarm -

UA814

BYPASS FREQUENCY

OUT OF RANGE

Bypass frequency fell out of inverter

synchronization follow-up range

CHECK BYPASS

INPUT

[3] Alarm -

UA817

EMERGENCY STOP

ACTIVATED

Emergency

stop

applied

-

- Alarm -

UA832

ASYNCHRONOUS

TRANSFER

Asynchronous transfer occurred

-

[2]

Alarm

-

UA834

BATTERY DEPLETED

AC OUT STOPPED

DC voltage dropped below discharge

end during inverter operation

-

- Alarm -

UA835

BATTERY DEPLETED

AND RESTART

Restart after battery depleted

-

-

Alarm

-

UA852 INVERTER

OVERLOAD

Total of more than 110% load during

MMS operation.

WARNING:

DECEASE

LOAD

[2] Alarm -

UA853

RETRY START

OPERATION

Continuous bypass voltage abnormal,

inverter stop, and 72B closed for 1 min.

will stop the UPS. (Fan stop)

[2]

Alarm

-