MITSUBISHI ELECTRIC 2033D SERIES UPS systems User Manual

Page 18

Advertising
background image



MITSUBISHI ELECTRIC 2033D SERIES UPS

MITSUBISHI
ELECTRIC

2033D SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

1-12


TABLE 1.3 Detail of Specifications

Rated Output kVA

30

50

80

Rated Output kW

24

40

64

AC INPUT

Configuration

3 phase, 3 wire

Voltage

480 V +15% to -15% (-30% can be operated)

Frequency

60 Hz (45.4Hz to 65Hz)

Reflected Current THD

4% typ. at 100% load; 7% typ. at 50% load

STATIC BYPASS INPUT

Configuration

3 phase, 3 wire

Voltage

480 V +/-10%

Frequency 60

Hz

BATTERY

Type Lead

Acid

Ride Through

Application Specific

Nominal Voltage

480 Vdc

Minimum Voltage

401 Vdc

Number of Cells

240

AC OUTPUT

Configuration

3 phase, 4 wire

Voltage

120/208 V, 277/480 V

Voltage Stability

+/-1%

Frequency 60

Hz

Frequency Stability

+/-0.05% in free running mode

Power Factor

0.8 nominal

Power Factor range

0.8 - 1.0 lagging (within output kW rating)

Voltage THD

2% typical THD at 100% Linear Load
5% typical THD at 100% non-linear load

Transient Response

+/-3% at 100% load step
+/-1% at loss/return of AC power
+/-3% at load transfer to/from static bypass

Transient Recovery

16.6ms

Inverter Overload

125% for 10 minutes, 150% for 1 minute

System Overload

1000% for 1 cycle

(with bypass available)

Bypass Overload

150% for 1 minutes

ENVIRONMENTAL

Cooling Forced

Air

Operating Temperature

32゚F ~ 104゚F (0゚C - 40゚C)
Recommended 68゚F - 86゚F (20゚C - 30゚C)

Relative Humidity

5% ~ 95% Non Condensing

Altitude

0 ~ 9000 feet No Derating

Location

Indoor (free from corrosive gases and dust)
(PCB conformally coated for use in industrial environment)

Paint Color

Munsell 5Y7/1 (Beige)

Advertising