C) Inverter supply at battery operation

FIGURE 1.3 Single Line Diagram - Battery Operation

Referring to Figure 1.3: In the event of AC input source failure or interruption, the
converter will de-energize and the battery will immediately discharge and supply DC
power to the inverter to maintain continuous AC power to the load. This operation will
continue until:
a) The battery capacity expires and the inverter turns off, or
b) Input power is restored after which the converter will power the inverter and critical

load and simultaneously recharge the batteries.


A fully charged battery will provide power for the specified time at the rated load, or longer,
at a reduced load.

When power is restored after a low battery shutdown, the converter automatically restarts
operation, recharges the batteries and the Inverter is automatically restarted without
operator intervention. Load is automatically assumed by the inverter without operator
intervention.

The power drawn by the load is equally shared between all system UPS during battery
operation.

UPS Module

Power Flow

Not in Use

AC input

CB

FB

72B

52RS

CONVERTER

INVERTER

Output

52C

52RC

FI

FO

BATTERY

User
supplied

52CS

Maintenance
Bypass
Switch

50kVA, 80kVA:
External Battery

Static Transfer

Switch

CB

AC Bypass

Input