MITSUBISHI ELECTRIC 2033D SERIES UPS systems User Manual

Page 19

Advertising
background image



MITSUBISHI ELECTRIC 2033D SERIES UPS

MITSUBISHI
ELECTRIC

2033D SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

1-13

TABLE 1.4 Rating of Contactors and Fuses

OUTPUT CAPACITY OF EQUIPMENT

2033D-B 2033D-A

2033D-B

30VA 50kVA 50kVA 80kVA

NUMBER APPLICATION

208V

480V

208V

480V

208V

480V 208V 480V

52RC AC

Input

Contactor

60A 100A

52C AC

Output

Contactor

60A 100A

52RS Bypass

Contactor

60A

100A

72B Battery

Disconnect

Contactor

80A 135A

200A

C
O
N

T
A

C

T

O
R

88RC Control

circuit

Contactor

90A

FIU, FIV, FIW

Inverter

Output Fuse

80A/660V 140A/660V

FOU, FOV, FOW

Inverter

Output Fuse

80A/660V 140A/660V

FUA, FUB, FUC

Control

Power Fuse

30A/600V

FSU, FSV, FSW

(Option)

Bypass

Input Fuse

140A/660V 280A/660V

FBP, FBN

DC Input

Fuse

125A/1250V 200A/1250V

350A/1250V

FZS1, 2, 3

Bypass Input

ZNR Fuse

16A/500V

FBS1, 2

Control

Power Fuse

10A/600V

FUF1, 2

Control

Power Fuse

10A/600V



F

U
S

E

FZR1, 2, 3

AC Input

ZNR Fuse

16A/500V

Advertising