MITSUBISHI ELECTRIC 2033D SERIES UPS systems User Manual

Page 37

Advertising
background image


MITSUBISHI ELECTRIC 2033D SERIES UPS

MITSUBISHI
ELECTRIC

2033D SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

3-5

TABLE 3.5 Recommended cable size and torque requirements

Input Side * 1, 2

Output Side * 1, 2

Bypass Side * 1, 2

DC Input Side * 1, 2

kVA

Capacity

Input

Voltage

Output

Voltage

Cable

Size

Torque

in. lbs

Cable

Size

Torque

in. lbs

Cable

Size

Torque

in. lbs

Cable

Size

Torque

in. lbs

480V 480V 6

AWG

or larger

42-56

in. lbs

6 AWG

or larger

42-56

in. lbs

6 AWG

or larger

42-56

in. lbs

4 AWG

or larger

100-135

in. lbs

30kVA

480V 208V 6

AWG

or larger

42-56

in. lbs

1 AWG

or larger

200-269

in. lbs

6 AWG

or larger

42-56

in. lbs

4 AWG

or larger

100-135

in. lbs

480V 480V 3

AWG

or larger

200 - 269

in. lbs

4 AWG

or larger

100-135

in. lbs

3 AWG

or larger

200 - 269

in. lbs

1 AWG

or larger

200-269

in. lbs

50kVA

480V 208V 3

AWG

or larger

200 - 269

in. lbs

3/0 AWG

or larger

347-469

in. lbs

3 AWG

or larger

200 - 269

in. lbs

1 AWG

or larger

200-269

in. lbs

480V 480V 1/0

AWG

or larger

200-269

in. lbs

1/0 AWG

or larger

200-269

in. lbs

1/0 AWG

or larger

200-269

in. lbs

4/0 AWG

or larger

347-469

in. lbs

80kVA

480V 208V 1/0

AWG

or larger

200-269

in. lbs

2x2/0 AWG

or larger

347 - 469

in. lbs

1/0 AWG

or larger

200-269

in. lbs

4/0 AWG

or larger

347-469

in. lbs

*1 – The cables must be selected to be equal to or larger than the sizes listed in the table.

*2 - Voltage drop across power cables not to exceed 2% of nominal source voltage -

*3 - Allowable ampere rating based on 75 C insulation at ambient temperature of 40 C

No more than 3 conductors in a raceway without de-rating.


Note : Copper conductors are assumed.