3.0 INSTALLATION AND OPERATION

3.1 Transportation and Installation

TABLE 3.1 How to transport and install the system

Transportation

Installation

Transport unit with forklift.
Carry with overhead crane using
eyebolts provided.

Using the pre drilled holes (4 - 24) in the
UPS channel base, anchor the unit using
appropriate hardware. (Not provided)

Note :

Do not transport in a horizontal position. Cabinets must be maintained

upright within +/- 15° of the vertical during handling

.

3.2 Installation Procedure

A) Note the load tolerance of the floor

Refer to Table 3.2 for list of UPS weights.

TABLE 3.2 List of UPS weights

UPS Capacity (kVA)

30

50

80

Weight (lb)

2060

1810

1990

B) Minimum clearance required for ventilation

Right side

1.0" (25 mm) (not required when sidecars are used)

Left side

1.0" (25 mm) (not required when sidecars are used)

Back side

0.0" (0.0 mm)

Top side

23.6" (600 mm) (for air flow)

C) Space requirement for routine maintenance

Allow for the following space at the time of installation.
Front

39.4" (1000 mm)

Sides

0.0" (0.0 mm)

Rear

0.0" (0.0 mm)