Terminals 33 to 34, 35 to 36 "Minor Fault” contact (OUT8)

Activated when a minor fault has occurred to the system.

Terminals 37 to 38, 39 to 40 "Total Alarm” contact (OUT9)

Activated when an alarm, a minor fault, or a major fault has occurred to the
system.

NOTE:

The UPS is equipped with a selectable output contact feature. The above

alarms are the default settings. Contact MITSUBISHI ELECTRIC
AUTOMATION, INC. for setup information

.

B) Input Contacts (for remote access of UPS)

External contacts are provided by the user of the UPS system. Terminal voltage at the
UPS is 24Vdc. Provide external dry contact accordingly.

NOTE:

Do not apply voltages to remote access input terminals. Damage to UPS

may result

.


Refer to Figure 2.17 for a typical wiring configuration. Although this figure applies to
the remote start/stop terminals, the same wiring arrangement is used for emergency
stop; battery liquid low; and battery temperature high.

FIGURE 2.17 Remote "Start" Contact Connections

Details of input contacts for remote access : TN2
Terminals 1 to 2

Remote "Inverter Start" input terminal (IN1)

Used to start inverter from a remote location. UPS must be programmed for
remote operation. Refer to Operations Menu for procedure.

Terminals 3 to 4

Remote "Inverter Stop" input terminal (IN2)

Used to stop inverter from a remote location. UPS must be programmed for
remote operation. Refer to Operations Menu for procedure.

Start

Relay Coil current : 8.3mA

Use Momentary Switches Only

UPS Cabinet

External to UPS
Cabinet

Relay

Coil

24 VDC

Start

Switch

Common

User supplied

0.5S - 4S
ON
OFF