Terminal ups cabinet external to ups, Cabinet, Relay coil – MITSUBISHI ELECTRIC 2033D SERIES UPS systems User Manual

Page 29: Nec class 2 power source, Relay, Contact, Terminal

Advertising
background image


MITSUBISHI ELECTRIC 2033D SERIES UPS

MITSUBISHI
ELECTRIC

2033D SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

2-10

A) Output Contacts (for external alarm annunciation)

Output contacts consist of form “A” dry type contacts. Rated capacity of all output

contacts is NEC Class2 (30Vdc/1Adc). All dry contacts should be operated at their
rated values or lower. Figure 2.16 illustrates a typical installation. The external relay
can also be a lamp, LED, computer, etc.

FIGURE 2.16 Control Wiring for External Contacts

Terminal

UPS Cabinet

External to UPS

Cabinet

Relay
Coil

NEC Class 2
Power Source

Relay

Contact

Terminal

Details of output alarm contacts : TN1
Terminals 1 to 2, 3 to 4 "UPS failure" contact

Activated when a major fault has occurred to the system.

Terminals 5 to 6, 7 to 8 "Load on Bypass" contact (OUT1)

Activated when the power is supplied from the static bypass input.

Terminals 9 to 10, 11 to 12 "Load on Inverter" contact (OUT2)

Activated when the power is supplied by the inverter.

Terminals 13 to 14, 15 to 16 "Battery Operation" contact (OUT3)

Activated when the battery is operating following an AC power failure.

Terminals 17 to 18, 19 to 20 "Converter Operation" contact (OUT4)

Activated when the converter is operating.

Terminals 21 to 22, 23 to 24 "Battery Low Voltage" contact (OUT5)

Activated when the battery voltage drops below discharge end voltage level
during inverter operation (i.e. During AC fail condition).

Terminals 25 to 26, 27 to 28 "Overload" contact (OUT6)

Activated when an overload has occurred to the system.

Terminals 29 to 30, 31 to 32 "Bypass Sync.” contact (OUT7)

Activated when the system is in sync. Mode.

User supplied

Advertising