Mitsubishi electric – MITSUBISHI ELECTRIC 2033D SERIES UPS systems User Manual

Page 49

Advertising
background image

MITSUBISHI
ELECTRIC

2033D SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

6-2

MITSUBISHI ELECTRIC 2033D SERIES UPS

Failure

Code List

Table 6.1 Fault Code

(Note 9)

Code

indication

Status message

Contents

Guidance

(Note 1)

Buzzer

(Note 2)
External

send-out

contact

(Note 3)

Failure

lamp

UF003

CONVERTER

ABNORMAL

Preliminary charge impossible

CALL SERVICE

ENGINEER

[1] Major

Lit

on

UF006

CONVERTER

ABNORMAL

Mixed operation (2 minutes)

CALL SERVICE

ENGINEER

[1] Major

Lit

on

UF055

CONVERTER

ABNORMAL

Mixed operation (1 minute)

CALL SERVICE

ENGINEER

[2] Minor

Flicker

UF056

CONVERTER

OVERCURRENT

IROC (C.F. 2.5) occurred 4 times in

one minute

CALL SERVICE

ENGINEER

[2] Minor

Flicker

UF102 DC OVERVOLTAGE

Over voltage of DC voltage

CALL SERVICE

ENGINEER

[1] Major

Lit

on

UF103 DC UNDERVOLTAGE

Low voltage of DC voltage

CALL SERVICE

ENGINEER

[1] Major

Lit

on

UF108

CHOPPER

OVERCURRENT

Chopper output overcurrent

CALL SERVICE

ENGINEER

[1] Major

Lit

on

UF151

DC VOLTAGE

ABNORMAL

Continuous +/-2% deviation of float

voltage under charging mode for 36 hrs

CALL SERVICE

ENGINEER

[2] Minor

Flicker

UF152

DC VOLTAGE

ABNORMAL

Does not return to equalizing voltage

after power supply is resumed

CALL SERVICE

ENGINEER

[2] Minor

Flicker

UF156

72B TRIPPED

(BATTERY OVERTEMP.)

Battery temperature abnormality

(UF157) lasted a long time (Note 5)

CHECK

BATTERY

[2] Minor

Flicker

UF157

BATTERY

OVERTEMPERATURE

Battery temperature abnormality

CHECK

BATTERY

[2]

Minor

(Note 4)

Flicker

UF161

72B TRIPPED

(DC VOLT. ABNORMAL)

Continuous condition of UF151 for

more than 12 hrs.

CALL SERVICE

ENGINEER

[2] Minor

Flicker

UF162 BATTERY

ABNORMAL

Battery abnormal detected by battery

self test.

CALL SERVICE

ENGINEER

[2] Minor

Flicker

UF163

BATTERY VOLTAGE

ABNORMAL

Battery voltage abnormality

CALL SERVICE

ENGINEER

[2] Minor

Flicker

UF201

INVERTER

OVERVOLTAGE

Output overvoltage during inverter

power supply (+ 15%)

CALL SERVICE

ENGINEER

[1] Major

Lit

on

UF202

INVERTER

UNDERVOLTAGE

Output low voltage during inverter

supply (-15%)

CALL SERVICE

ENGINEER

[1] Major

Lit

on

UF203

INVERTER

OVERCURRENT

Inverter output overcurrent

CALL SERVICE

ENGINEER

[1] Major

Lit

on

UF209 52C ABNORMAL

52C not turned ON

CALL SERVICE

ENGINEER

[1] Major

Lit

on

UF210 52C ABNORMAL

52C not turned OFF

CALL SERVICE

ENGINEER

[1] Major

Lit

on

Advertising