Rack Mounting

Cabling

Caution:

Flat SCSI cables need a minimum rack depth of 27 inches, and
the rack must be EMI/RFI shielded. Round SCSI cables need a
minimum rack depth of 29 inches.

Caution:

The library unit should be properly grounded to the rack
equipment. This ground connection must be maintained when
the supply connection is other than a direct connection to the
branch circuit.

Operating Environment

Caution:

Installing library units in a rack system must not reduce the air
flow within the rack. The maximum recommended ambient
temperature for the library is 89.6

°F (32°C).

Power

Caution:

Make sure the power requirements of the library plus the
cumulative power draw of the other equipment in the rack do
not overload the supply circuit and/or wiring of the rack.

Safety

Warning:

The library weighs approximately 61 pounds. Use caution when
lifting the library to install it in a rack. Ask for help when lifting
the library.

Warning:

Always stack the rack from the bottom up to ensure a stable and
safe rack.