P051 maximum volume – Siemens sitrans LU01 User Manual

Page 39

Advertising
background image

7ML19985BE02

SITRANS LU01 – INSTRUCTION MANUAL

Page 33

m

mmmm

Pa
ra

m

e

te

rs

P051 Maximum Volume

For Readings in volumetric units (rather than percent), enter the vessel volume between

Empty (P006) and Span (P007).

Any volume units can be chosen because volume is calculated from empty to maximum
span and is scaled according to the Tank Shape (P050) value.

Values

7

Parabola Ends

8

Sphere

9

Universal Linear

10

Universal Curved

Alters

P001 Operation

P051 Maximum Volume

P920 Reading Measurement

Values

Range: 0.000 to 9999
Preset: 100.0

Alters

P060 Decimal Position

Related

P006 Empty

P007 Span

P924 Volume Measurement

Note:

Make sure selected chosen units allow LCD volume display.

Examples:

If max. volume = 3650 m

3

, enter 3650

If max. volume = 267500 gallons, enter 267.5 (thousands of gallons)

Advertising