Independent relay setpoints – Siemens sitrans LU01 User Manual

Page 49

Advertising
background image

7ML19985BE02

SITRANS LU01 – INSTRUCTION MANUAL

Page 43

m

mmmm

Pa
ra

m

e

te

rs

To reset the Relay Function to use Standard Alarms, enter the desired Relay Set Up
(P100).

Independent Relay Setpoints

Relay ON and OFF Setpoint values set the critical points (based on the Relay Function)
where, in RUN mode:

Relay status indicators are switched ON and OFF

Alarm Indicators (if programmed) are switched ON or OFF

Relays are

energized and de-energized

For most Relay Functions, setpoint values represent material levels, entered in Units
(P005) or percent of Span (P007) as referenced to Empty (P006). Temperature alarm
values are entered in degrees Celsius (°C).

Rate alarms are entered in Units / minute or percent of Span per minute. A positive value
is entered for a filling rate alarm; negative for emptying.

Values For P111

Control

Type

#

1

1.

When reading and setting this parameter through Modbus or SmartLinx
communications the parameter values are mapped to different numbers.
See the relevant SmartLinx manual for Modbus information.

Relay Control

General

Off

0 Relay set off, no action (preset)

Level

1* Based on level setpoints ON and OFF

In Bounds

2

When level enters the range between ON and OFF
setpoints

Out of Bounds

3

When level exits the range between ON and OFF set-
points

Rate of Change

4 Based on rate setpoints ON and OFF

Temperature

5 Based on temperature setpoints ON and OFF

Loss of Echo (LOE)

6 When echo is lost

Cable Fault

7 When the circuit to a transducer is opened

Pump

Fixed Duty Assist

50

At fixed ON and OFF setpoints and allows multiple
pumps to run or for rake control

Advertising