P112 relay on setpoint, P113 relay off setpoint, P116 dead band – Siemens sitrans LU01 User Manual

Page 51

Advertising
background image

7ML19985BE02

SITRANS LU01 – INSTRUCTION MANUAL

Page 45

m

mmmm

Pa
ra

m

e

te

rs

P112 Relay ON Setpoint

Sets the process point at which the relay changes from its NORMAL state.

For most applications, the relay is tripped at this point. For IN-BOUNDS and OUT-OF-
BOUNDS alarms, it is the high point in the specified range. This parameter is set
according to Span (P007) even when another reading, such as volume, is shown on
the LCD.

P113 Relay OFF Setpoint

Sets the process point at which the relay returns to its NORMAL state.

For most applications, the relay is reset at this point. For IN-BOUNDS and OUT-OF-
BOUNDS alarms, it is the low point in the specified range. This parameter is set according
to Span (P007), even when another reading, such as volume, is shown on the LCD.

P116 Dead Band

The distance above and below the bound alarm setpoints.

Primary Index

Relay

Values

Range: -999 to 9999
Preset: ----

Altered by

P007 Span

Related

P100 Preset Applications

P111 Relay Control Function

P113 Relay OFF Setpoint

Note:

Relay ON and Relay OFF setpoint values cannot be exactly equal.

Primary Index

Relay

Values

Range: -999 to 9999
Preset: ----

Altered by

P007 Span

Related

P100 Preset Applications

P111 Relay Control Function

P112 Relay ON Setpoint

Primary Index

Relay

Values

Range: 0.000 to 9999
Preset: 2% of span

Related

P111 Relay Control Function

P112 Relay ON Setpoint

P113 Relay OFF Setpoint

Advertising