SITRANS LU01 – INSTRUCTION MANUAL

7ML19985BE02

Pa

ra

m

e

te

rs

Installation Records (P340 to P342)

P340 Date of Manufacture

View the date of manufacture of this SITRANS LU01 unit.

P341 RUN Time

View the number of days this SITRANS LU01 has been in operation.

The RUN Time value is updated once a day, and cannot be reset. However, in the event of
a power interruption, the counter won’t advance. Therefore, a unit that is powered down
on a regular basis will not have an accurate value.

P342 Start Ups

The number of times power has been applied since the Date Of Manufacture.

Range Calibration (P650 to P654)

There are two types of calibration possible:

Offset:

Adjusts the measurements by a fixed amount.

Sound Velocity: Adjusts speed of sound and changes the measurement calculations.

Do Offset calibration at any steady level unless a Sound Velocity calibration is also done.
If both calibrations are done then do Offset at a known high level and Sound Velocity at a
known low level.

P650 Offset Calibration

Calibrates Empty (P006) if the reported level is consistently high or low by a fixed amount.

Values

Format: YY:MM:DD (view only)

Related

P341 RUN Time

P342 Start Ups

Values

Range: 0.000 to 9999 (view only)

Related

P340 Date of Manufacture

P342 Start Ups

Values

Range: 1 to 9999 (view only)

Related

P340 Date of Manufacture

P341 RUN Time

Values

Range: -999 to 9999

Related

P006 Empty

P062 Offset Reading

P652 Offset Correction

P664 Temperature