Failsafe (p070 to p072), P062 offset reading, P070 failsafe timer – Siemens sitrans LU01 User Manual

Page 43

Advertising
background image

7ML19985BE02

SITRANS LU01 – INSTRUCTION MANUAL

Page 37

m

mmmm

Pa
ra

m

e

te

rs

P062 Offset Reading

Adds the specified value to the level reading, usually to reference the reading to sea level

or another datum level.

The operation of the device is not affected by the Offset Reading. This value is used for
display purposes only. All control measurements are still referenced to Empty.

Failsafe (P070 to P072)

As preset, in the event of a measurement or technical difficulty, the SITRANS LU01 holds
the Reading, Bar Graph, mA outputs, and relays at their last known values.

To operate process control equipment under these conditions, alter the following
parameters as required.

P070 Failsafe Timer

The time for invalid measurements to elapse before Failsafe State activates.

In the RUN mode, when a difficulty first occurs, the Reading, Bar Graph, relay status, and
mA outputs are held at last known values and the Failsafe Timer is activated.

When a valid measurement is made before the timer expires, the SITRANS LU01
advances to the new material level (if changed) as normal (per Measurement Response,
P003) and the timer resets.

Values

Range: -999 to 9999
Preset: 0.000

Related

P920 Reading Measurement

Values

Range: 0.0 to 9999
Preset 10.00 minutes

Altered by

P003 Maximum Process Speed

Related

P129 Relay Failsafe

vessel

vessel

sea level

display offset (P062)

Advertising