Ma output trim (p214 to p215), P213 ma output max limit, P214 4 ma output trim – Siemens sitrans LU01 User Manual

Page 55

Advertising
background image

7ML19985BE02

SITRANS LU01 – INSTRUCTION MANUAL

Page 49

m

mmmm

Pa
ra

m

e

te

rs

Preset is determined by mA Function (P200). If P200 = 1 or 3, then the preset is 0.0, or if
P200 = 2 or 4, then the preset is 3.8. For P200=1 or 3 (preset is 0.0), this parameter has no
effect because the minimum limit cannot be negative, and the minimum current is always
0.0 mA.

P213 mA Output Max Limit

Sets the maximum mA output value (in mA) to be produced.

mA Output Trim (P214 to P215)

This does not affect the P203 value shown, and is used when recalibration of an external
device is impractical.

P214 4 mA Output Trim

Calibrates the 4 mA output.

Adjust this value so the device indicates 4.000 mA when P214 is accessed.

P215 20 mA Output Trim

Calibrates the 20 mA output.

Adjust this value so the device indicates 20.00 mA when P215 is accessed.

Primary Index

mA output

Values

Range: 0.000 to 22.00
Preset: 20.2 mA

Related

P200 mA Output Range / P212 mA Output Min LImit

Primary Index

mA output

Values

Range: -1.00 to 1.000
Preset: 0.000

Related

P215 20 mA Output Trim

Primary Index

mA output

Values

Range: -1.00 to 1.000
Preset: 0.000

Related

P214 4 mA Output Trim