Altivar, 58 trx ac drives, Wiring recommendations – Schneider Electric ALTIVAR 58 TRX User Manual

Page 111

Advertising
background image

Altivar

®

58 TRX AC Drives

Wiring Recommendations

111

09/2003

©

2000–2003 Schneider Electric All Rights Reserved

Wiring Diagram for ATV58 TRX Type F Controllers (Single Phase)

M

3

φ

Brake

Resistor

(5)

PA

PB

ATV58E

Other Models

T1

T2

T3

U

V

W

+

-

ATV58E

U09M2FZU

and U18M2FZU

Brake

Module

Brake

Resistor

PA

PB

+

-

(5)

(2)

L1

L2

(4)

(6)

R1A

R1C

R1B

K13

K14

AO

1

COM

AI1

+10

COM

AI2

LI3

LI1

LI2

+24

LI4

Fault

Manual

Speed

Potentiometer

(3)

L1

L2

F1

F2

(1)
Line
Reactor

Start-Stop Push Buttons

with Seal-in Relay

ST

OP

ST

AR

T

Notes

1. Line inductor, if required.

2. Fault relay contacts for remote signalling of the drive controller state. Contact state is shown with

the controller de-energized or faulted.

3. User-installed wiring for using LI2, LI3, and LI4 with internal +24 V power supply. When using a

+24 V external supply, connect the 0 V to the COM terminal. Do not use the +24 terminal on the
control board but connect logic inputs to external +24 V.

4. K13 and K14 are open terminals available for customer use.

5. Use dynamic braking module VW3A58701 with drive controllers ATV58EU09M2FZU and

U18M2FZU if dynamic braking is required. See page 34 for available braking resistor kits.

6. Manual speed potentiometer and start-stop push buttons are factory-installed in the enclosure

cover. There is enough space in the cover to install one more 16-mm operator.