Altivar

®

58 TRX AC Drives

Wiring Recommendations

©

2000–2003 Schneider Electric All Rights Reserved

112

09/2003

Wiring Diagram for ATV58 TRX Type F Controllers (Three Phase)

M

3

φ

Brake

Resistor

(5)

PA

PB

T1

T2

T3

U

V

W

(2)

L1

L3

(4)

R1A

R1C

R1B

K13

K14

AO

1

COM

AI1

+10

AI2

LI3

LI4

Fault

Manual

Speed

Potentiometer

(3)

L1

L3

F1

F2

(1)
Line
Reactor

L2

L2

F3

COM

LI1

LI2

+24

Start-Stop Push Buttons

with Seal-in Relay

(6)

ST

OP

ST

AR

T

3

P

h

as

e T

y

pe

F

.ep

s

Notes

1. Line inductor, if required.

2. Fault relay contacts for remote signalling of the drive controller state. Contact state is shown with

the controller de-energized or faulted.

3. User-installed wiring for using LI2, LI3, and LI4 with internal +24 V power supply. When using a

+24 V external supply, connect the 0 V to the COM terminal. Do not use the +24 terminal on the
control board but connect logic inputs to external +24 V.

4. K13 and K14 are open terminals available for customer use.

5. See page 34 for the available braking resistor kits.

6. Manual speed potentiometer and start-stop push buttons are factory-installed in the enclosure

cover. There is enough space in the cover to install one more 16-mm operator.