ATV58 TYPE FVC SPECIFICATIONS

Environmental Specifications

NOTE: Discoloration of drive controller plastic pieces will occur if exposed to direct sunlight.

Enclosure type

ATV58HU18N4 to U90N4: IP21/open type controllers according to Standard EN50178.
ATV58HD12N4 to D79N4: Type 1 with conduit entry kit.

Resistance to vibrations

According to IEC 60068-2-6: 1.5 mm zero to peak from 3 to 13 Hz, 1 gn from 13 to 200 Hz

Resistance to shocks

According to IEC 60068-2-27: 15 g, 11 ms

Ambient pollution degree ATV58HU18N4–D23N4: Pollution degree 2 conforming to IEC 600664-1, EN50718 and NEMA ICS-1, Annex A.

ATV58HD28N4–D79N4: Pollution degree 3 according to IEC 600664-1, EN50718 and NEMA ICS-1, Annex A.
Protect the drive controller against dust, corrosive gas, and falling liquid.

Max. relative humidity

95% maximum, non-condensing and without dripping according to IEC 60068-2-3. Provide heating system if there is
condensation.

Maximum ambient
temperature

Storage:

-25 to +65 °C (-13 to +149 °F)

Operation: Drive controllers ATV58HU18N4 to U90N4:

-10 to +50 °C (+14 to 122 °F) without derating
-10 to +60 °C (+14 to 140 °F) with fan kit

and derating of the current 2.2% per °C above 50 °C

Drive controllers ATV58HD12N4 to D79N4:

-10 to +40 °C (+14 to 104 °F) without derating
-10 to +50 °C (+14 to 122 °F) with fan kit

and derating of the current 2.2% per °C above 40 °C

Altitude

3300 ft (1000 m) maximum without derating; derate the output current by 1% for each additional 330 ft (100 m)

Operational position

Vertical, ±10°, with power terminals at the bottom.

See page 33.

See page 33.

Electrical Specifications

Input voltage

400 V -15% to 460 V + 20% three phase input

Input frequency

50/60 Hz ±5%

Output voltage

Three-phase output, maximum voltage equal to input voltage

Galvanic isolation

Galvanic isolation between power and control (inputs, outputs, supplies)

Output frequency

0 to 60 Hz (configurable to 450 Hz with programming options)

Switching frequency

4 kHz, configurable with programming options

ATV58HU18N4–D23N4:

0.5 - 1 - 2 - 4 - 8 kHz without derating
12 - 16 kHz with derating in steady state
12 - 16 kHz without derating and with reduced duty cycle

ATV58HD28N4–D46N4:

0.5 - 1 - 2 - 4 kHz without derating
8 - 12 kHz with derating in steady state
8 - 12 kHz without derating and with reduced duty cycle

ATV58HD54N4–D79N4:

0.5 - 1 - 2 kHz without derating
4 - 8 kHz with derating in steady state
4 - 8 kHz without derating and with reduced duty cycle

Speed range

1:100 Open loop. 1:1000 Closed loop.

Speed regulation

1% of rated motor speed without adjustments or feedback.

±0.01% of rated motor speed with appropriate encoder feedback.

Efficiency

97% at full load typical.

Displacement power
factor

98% through speed range.

Motor control algorithm

Sensorless flux vector control with a pulse width modulated (PWM) output wave form.

Braking torque

30% of nominal motor torque without dynamic braking (typical value). Up to 150% with dynamic braking option.

Transient output current

160% of nominal NEC rated motor current for 60 seconds (for constant torque ratings).
110% of nominal motor current for 60 seconds (for variable torque ratings).

Transient motor torque

200% of nominal motor torque (typical value at ±10%) for 2 seconds.
170% of nominal motor torque (typical value at ±10%) for 60 seconds.

Accessories are described starting on page 26.

The drive controller can be configured to reduce switching frequency if the drive thermal state reaches 95%. When the drive thermal state returns
to 70%, the switching frequency returns to the set value. If the duty cycle (drive controller run time) does not exceed 60% (36 second maximum for
a 60 second cycle) derating is not required.