The ATV58 TRX family of adjustable-frequency AC drive controllers is used
to control three-phase asynchronous motors. The ATV58 TRX Type E model
contains an ATV58 TRX Type H drive controller packaged in a compact, Type
1 enclosure. It is for use in mechanical rooms, OEM equipment, and factory
floor applications. The following Type E drive controller models are available:

• 1 to 7½ hp (0.75 to 5.5 kW), 400/460 Vac, three-phase input

• ½ to 3 hp (0.37 to 2.2 kW), 200/240 Vac, single-phase input

• 2 to 3 hp (1.5 to 2.2 kW), 200/240 Vac, three-phase input

Each ATV58 TRX Type E drive controller contains:

• A GV2 manual motor starter, ATV58 TRX drive controller, and an output

contactor

• A three-position selector switch wired for “RUN FORWARD”

• A manual speed potentiometer mounted on the front of the enclosure

• Space for two additional 16-mm operators

• Four conduit openings that are closed with plugs

• A transparent plastic door for viewing the status LEDs and a separately-

supplied keypad

All ATV58 TRX communication and I/O options can be used in the Type E
controllers. The Type E drive controllers can be used on constant or variable
torque applications. The ratings are shown in the tables below.

200 Vac -10% / 240 Vac +10% at 50/60 Hz ±5%, Single-Phase Input with 3-Phase Output

Frame
Size

Drive Controller
Catalog Number

Motor Power

Rated
Output Current

Transient
Output Current

kW

HP

A

A

1

ATV58EU09M2ZU

0.37

0.5

2.3

3.1

1

ATV58EU18M2ZU

0.75

1

4.1

5.6

2

ATV58EU29M2ZU

1.5

2

7.8

10.6

3

ATV58EU41M2ZU

2.2

3

11

15

200 Vac -10% / 240 Vac +10% at 50/60 Hz ±5%, 3-Phase Input with 3-Phase Output

Frame
Size

Drive Controller
Catalog Number

Motor Power

Rated
Output Current

Transient
Output Current

kW

HP

A

A

2

ATV58EU29M2ZU

1.5

2

7.8

10.6

3

ATV58EU41M2ZU

2.2

3

11

15

400 Vac -10% / 460 Vac +10% at 50/60 Hz ±5%, 3-Phase Input with 3-Phase Output

Frame
Size

Drive Controller
Catalog Number

Motor Power

Rated
Output Current

Transient
Output Current

kW

HP

A

A

2

ATV58EU18N4ZU

0.75

1

2.3

3.1

2

ATV58EU29N4ZU

1.5

2

4.1

5.6

2

ATV58EU41N4ZU

2.2

3

5.8

7.9

3

ATV58EU54N4ZU

3

7.8

10.6

3

ATV58EU72N4ZU

4

5

10.5

14.3

3

ATV58EU90N4ZU

5.5

7.5

13

17.7

For dimensions, see page 122; for wiring diagrams, see pages 109 and 110.

Power indicated is for a switching frequency between 0.5 and 4 kHz, and at steady state. For switching

frequency between 8 and 16 kHz, use the next largest size drive controller. (For example, for 2 hp, order drive
controller ATV58EU41M2ZU.) If the duty cycle (that is, the drive controller run time) does not exceed 60% (36
second maximum for a 60 second cycle), this is not necessary.

For 60 seconds.

A line reactor (3% minimum) must be used with this drive controller.