Altivar, 58 trx ac drives, Wiring recommendations – Schneider Electric ALTIVAR 58 TRX User Manual

Page 110

Advertising
background image

Altivar

®

58 TRX AC Drives

Wiring Recommendations

©

2000–2003 Schneider Electric All Rights Reserved

110

09/2003

Wiring Diagram for ATV58 TRX Type E Controllers (Three Phase)

M

3

φ

Brake

Resistor

(5)

PA

PB

T1

T2

T3

(2)

L1

L3

(4)

(6)

R1A

R1C

R1B

K13

K14

+10

AO

1

AI1

COM

AI2

+24

LI1

LI2

LI3

LI4

(6)

0

Fw

3

3

1

1

Fault

Manual

Speed

Potentiometer

Drive

Run

Stop

Stop

Fw

Run

Fwd

[7]

1

3

O

(3)

L1

L3

F1

F2

(1)
Line
Reactor

L2

L2

F3

U

V

W

Notes

1. Line reactor, if required.

2. Fault relay contacts for remote signalling of the drive controller state. Contact state is shown with

the drive controller de-energized or faulted.

3. Internal +24 V. When using a +24 Vdc external supply, connect the 0 V to the COM terminal. Do

not use the +24 V terminal on the control board, but connect logic inputs to external +24 V.

4. Auxiliary on output contactor. If the controller is re-programmed, the R2 function must be

assigned to Output Contactor Command.

5. See pages 34–37 for the available braking resistor kits.

6. Manual speed potentiometer and three-position switch are factory-installed in the terminal block

cover. There is enough space in the terminal block cover to install two more 16-mm operators.

7. When user-installed wiring is added from terminals +24 to LI2 and when the drive controller

programming is at the factory settings, placing the selector switch in this position will command
the controller to run in reverse. The function of LI2 can be changed using one of the available
programming tools. See page 26 for a list of programming tools.