INSTALL THE SUCTION BRACKET

Position the suction bracket assembly in the desired

installation location. Consider locating the suction

assembly on a piece of 2x6 if needed to provide better

clearance with the finished basin material. The

center of the suction cover must be located between

2Ć1/2 and 3Ć1/2Ćinches up from the estimated finished

floor surface. Do not secure the suction bracket

assembly in place at this time.
NOTE: Water drainage of the entire Custom

BodySpa system occurs through the suction assembly.

Do not use flexible tubing for the suction line. Use

straight sections of rigid PVC tubing and at most one

additional elbow or fitting if needed. Always

maintain a minimum 1/4Ćinch per foot pitch toward

the suction assembly when measuring and

connecting the piping. Do not use elbows to change

the vertical direction of the tubing.
Measure and cut a length of 1Ć1/2Ćinch (I.D.) rigid

PVC tubing to connect the suction housing to the

pump inlet. Do not solvent weld the PVC connections

at this time. Use a level and measuring tape to ensure

a minimum 1/4Ćinch per foot pitch toward the

suction fitting to provide adequate drainage.
NOTE: Refer to the minimum waterline height

information on the side of the pump box to determine

the maximum pump box height.
If the suction line does not provide the necessary

1/4Ćinch per foot pitch, shim under the pump box to

raise the pump box slightly to achieve the correct

pitch. Then remove the four drywall screws from the

mounting frame, and raise the mounting frame the

same distance you raised the pump box. ReĆinstall

the four drywall screws, and tighten securely.
NOTE: If you raise the pump box and tower height,

you must also plan to increase the footbath basin

minimum water level accordingly. This will increase

the threshold height and minimum 9Ćinch water

depth. Failure to do so will prevent the pump from

priming.
Install the remaining six drywall screws to the

mounting frame, and tighten securely.

Check Point #4

-

Suction bracket assembly is positioned.

-

Rigid 1Ć1/2Ćinch (i.d.) pvc tubing measured, cut, and fit, but not

solvent welded.

-

Waterline height confirmed using the label on the pump box.

-

Minimum pitch of 1/4Ćinch per foot from pump inlet connection to

suction housing.

-

Tower mounting frame is permanently secured.