Karcher WATERCLEAN 600 CD User Manual

Page 17

Advertising
background image

17

WTC 600 LP / MP

DESCRIPTION

Service Handbook 08.2004

2.4

Technical Data WTC 600 LP/MP

Parameter

WTC 600 LP

WTC 600 MP

Ambient temperature

+1°C - +50°C

Storage temperature (delivery)

to -10°C

Humidity

<100% r.F.

Supply voltage

3*400V 50 Hz

1)

1*230V 50 Hz

1)

Pre-filter controls: prim / sec.

230 V/12 V 50 Hz

Metering pumps

230 V 50-60Hz

Wiring

3 Ph, N, PE

Electrical protection

16 A

Connected electrical load

2.2 kW

2.2 kW

Effective electrical power consumption

1.5 kW

2.2 kW

Mechanical protection / protection against water

Switch cabinet

IP44

Pump and valves

IP44

Metering pump

IP44

Power outlets (plug inserted)

< IP44

Minimum temperature of untreated water

+5°C

Maximum temperature of untreated wate

+35°C

Reference temperature

+15°C

pH-value, untreated water

6-9.5

pH-value during cleaning

3-11

System input pressure and flow

2-6 bar at min. 2 m³/h

Capacity range

15000 l/day (±10%)

Maximum drinking water capacity

650 l/h

Dimensions: H x W x D

WTC 600 LP/MP

1800 x 660 x 720 mm

WTC 600 LP/MP - A

1800 x 1120 x 720 mm

WTC 600 LP/MP - AM

1800 x 1120 x 720 mm

Weight in delivery condition (without filter container)

WTC 600 LP/MP

135 kg

WTC 600 LP/MP - A

155 kg

WTC 600 LP/MP - AM

175 kg

Table 3

Technical Data

1)

depending on the system version