MAINTENANCE

WTC 600 LP / MP

Service Handbook 08.2004

4.5

Malfunction, Cause and Corrective Action

4.5.1

Metering Station LED and Indicator LEDs at the Switch Cabinet

Indication

Malfunction

Cause

Corrective Action

Chap./
Fig.

Red fault LED

Pump in metering

Metering

Refill, check float switch

2.3.1.5,

lights

station blocked

container empty

3.2,3.3.2.4

Sensor signal

Check sensors,

2.3.1.5,

missing

check bridges in

ETL, 3.3.2

switch cabinet,
check sensor
wiring

Red

Backwashing of

Not necessary, as

2.3.1.5

regeneration

the sand filter or

the equipment

LED lights

activated carbon automatically
filter active

switches on again

Red tank full

Float switch in the

Drinking water

Not necessary, as

2.3.1.5,

LED lights

drinking water tank tank full

the equipment

3.3.2.4

has switched

automatically
switches on again;

Switch defective

Check switch, replace if
necessary

Table 27

Malfunction indications at the switch cabinet and their causes

Indication

Malfunction

Cause

Corrective Action

Chap./
Fig.

Green LED at

LED does not

No power supply Have fuse Q2

metering station flash when

checked from

pump does not

high-pressure

electrician

flash

pump runs

Operating mode

Set operating mode switch (1/10)

contact

to manual

Electrical defect

Replace pump

ETL

Red LED at

Pump blocked

Metering

Refill, check float switch

3.2,

metering

container empty

3.3.2.4

station pump
lights red

Cable that

Have cable checked

3.3.2.3

indicates empty
is broken

Auxiliary

Have auxiliary contactor

ETL, SLP

contactor in

replaced by electrician

switch cabinet
defective

Table 28

Metering station and metering pump LED