High water temperature shutdown switch, High exhaust temperature shutdown switches, Figure 2-3. high water temperature shutdown switch – Kohler 3.5CFZ User Manual

Page 26

Advertising
background image

TP-5695 12/93

Operation 2-5

High Water Temperature

Shutdown Switch

The high water temperature shutdown switch protects
the engine against internal damage if the cooling water
temperature in the engine block is too high due to
cooling water or coolant circulation problems. The
switch is set to trip at 248--266°F (120--130°C). The
location of the high water temperature shutdown switch
is shown in Figure 2-3.

TOTAL HOURS

0

0

0

0

0

1/10

10A

FUSE

START

STOP

BATT.

CHRG.

INPUT

258000-D

1 (hidden)

1. High Water Temperature Shutdown Switch

Figure 2-3. High Water Temperature

Shutdown Switch

High Exhaust Temperature

Shutdown Switches

The two high exhaust temperature shutdown switches
protect the engine against internal damage due to
excessive exhaust temperatures. The switches are set
at 210--220°F (99--105°C). The locations of the high
exhaust temperature shutdown switches are shown in
Figure 2-4.

TOTAL HOURS

0

0

0

0

0

1/10

10A

FUSE

START

STOP

BATT.

CHRG.

INPUT

258000-D

1

1. High Exhaust Temperature Shutdown Switches

(one located on each manifold)

Figure 2-4. High Exhaust Temperature

Shutdown Switches