4-4 Troubleshooting

Generator

Problem

Possible Cause

Corrective Action

No AC output

Circuit breaker in OFF position

Reset breaker to ON position

No AC output

Circuit breaker tripped due to overload on
generator set

Reduce load. See Wattage Requirements.
Reset breaker to ON position.

Ship-to-shore transfer switch in “OFF”or
“SHORE”position

Turn switch to generator power

No DC power to controller

Check battery connections

Controller fuse blown

Replace fuse

Generator malfunction such as capacitor
or other internal fault

See authorized Kohler service
dealer/distributor

Low output or
excessive drop in

Engine speed too low

Adjust governor

Low output or
excessive drop in
voltage

Generator overloaded

Reduce load. See Wattage Requirements.

voltage

Engine in poor condition

If routine services are performed and
condition persists, see authorized Kohler
dealer/distributor

Defective capacitor

See authorized Kohler service
dealer/distributor

High generator
output voltage

Defective capacitor and/or poor wiring
connections

See authorized Kohler service
dealer/distributor

output voltage

Excessive speed or frequency

Adjust governor. Check governor linkage
and spring for damage or binding.

Will not crank

No DC power to controller

Check battery connections

Will not crank

Controller circuit fuse blown

Replace fuse and attempt start-up. If fuse
blows again, contact authorized Kohler
service dealer/distributor.