6-14 Installation

Remote Start Switch Connection

Kohler offers several remote panels for connection to
the generator set. See Accessories for further detailed
description. A wiring harness with a connector keyed to
the controller box connector is available to connect
these panels to the generator set. The other end of this
harness has pigtails which can be used if the installer

elects to use just a start-stop switch or separate lights
and hourmeter. See Figure 6-22.

NOTE

If gauges are to be used, there must also be generator
set senders. Senders are optional on these generator
sets. Gauges and senders are available as service
items

from

an

authorized

Kohler

service

dealer/distributor.

WT

OP

1

2

3

4

5

6

J3

Lead Designations

Pin

Lead

Function

J3-1

Black

Ground (--)

J3-2

Tan

Water Temp. Ga.

J3-3

Lt. Blue

Oil Pressure Ga.

J3-4

Violet

Gen. “ON”(+)

J3-5

Yellow/Red

Start

J3-6

Grey/Black

Stop

NOTE

All wire is 16 gauge.

Tape to insulate all

unused lead ends.

1

2

3

4

6

7

5

1. Use Insulink or Solder Connection (Tape to Insulate)
2. Hourmeter
3. “ON”Light
4. Stop

5. Start
6. Rocker Switch
7. Gauges Senders

Figure 6-22. Remote Control Panel Wiring