TP-5695 12/93

Wiring Diagrams 5-5

120/240- or 110/220-Volt

Configuration--Figure 5-6

Jumper lead not used. If unit was originally wired for
straight 120 or 110 volt, be sure jumper lead is removed
(see Figure 5-6 for location). Leads L1 and L2 are
different phases and must never be connected together.

4

3

2

1

Stator Leads

LO
GRD.
L2
L1

LO (Neutral)

Load Side

Line Side

Circuit

Breaker

Ground

60 Hz

50 Hz

L0--L1

120 volt

110 volt

L0--L2

120 volt

110 volt

L1--L3

240 volt

220 volt

Figure 5-6. Without Jumper Lead