5-4 Wiring Diagrams

TP-5695 12/93

Four-Lead Reconnectable (Single-Phase) Generator Sets Where Generator

Output Can Be Reconnected For 120 volt or 120/240 volt, 60 Hz,

110 volt or 110/220 volt, 50 Hz

NOTE

When a generator set is reconnected to a voltage
different than nameplate voltage, notice should be
placed on the unit indicating this change. Decals for this
purpose are available from authorized Kohler
dealers/distributors.

120- or 110-Volt 3-Wire 2-Pole

Configuration--Figure 5-4

Jumper lead to be placed on line side of circuit breaker.
Leads L1 and L2 can either be left as separate leads or
can be connected together depending upon which is
practical for the given application. Regardless of the
number of phase (black) leads used in the application,
both circuit breakers must have leads attached to the
load side. It is recommended that jumper lead be
maintained for all straight 120- or 110-volt systems since
it helps balance the load of the generator set.

4

3

2

1

Stator Leads

LO
GRD.
L2
L1

LO (Neutral)

Ground

Load Side

Line Side

Circuit

Breaker

Jumper

Lead

60 Hz

50 Hz

L0--L1

120 volt

110 volt

L0--L2

120 volt

110 volt

Figure 5-4. With Jumper Lead

120- or 110- Volt 2-Wire Configuration

Figure 5-5 (Single Pole)

If the installation requires a 120 or 110 volt, 2-wire
system, a single-pole circuit breaker must be used. See
Figure 5-5. When connecting stator phase leads
together, the output lead (L1) must be sized accordingly.

4

3

2

1

Stator Leads

LO

GRD.

LO (Neutral)

Ground

Load

Side

Line

Side

1-Pole

Circuit

Breaker

L1

60 Hz

50 Hz

L0--L1

100-120 volt

100-120 volt

Figure 5-5. 120 Volt, 2-Wire