3 setting bitpacked options with the terminal, Setting bitpacked options with the terminal, N 12.1.3 - setting – Liebert STS2 User Manual

Page 100: Bitpacked options with the terminal

Advertising
background image

Communication Interfaces

92

12.1.3 Setting Bitpacked Options With the Terminal

Five sets of options and features settings are available through the terminal to control the system

operation.
Under System Settings for the SPT command, these items denote which options are INSTALLED:

• 6 — Options_1
• 14 — Comms Options 1
• 15 — Comms Options 2

Under User Settings, for the SPT command, these items denote which features are ENABLED:

• 17 — Critical Option Enabling
• 18 — Non-Critical Option Enabling

The value parameter settings are in the form of a bit-packed word (in hexadecimal notation). In other

words, each bit indicates a particular setting for the option or feature. The bit assignments for the

options and features are as follows:
Options_1

bit0 —HasDualOutputBreaker
bit1 — HasPDU
bit2 — Has4PoleTransferSwitch
bit3 — HasShuntTrip
bit4 — HasWyeOutputXfmr
bit5 — HasExternalPrecisionTimeSource
bit6 — HasSFA
bit7 — HasRemoteSourceSelect
bit8 through bit15 — not used (set to 0)

Comms Options 1

bit0 — HasIntModem
bit1 — HasExtModem
bit2 — HasNIC
bit3 — not used (set to 0)
bit4 — HasSiteScan
bit5 — not used (set to 0)
bit6 — not used (set to 0)
bit7 — HasOpenCommsDigitalInputBrd
bit8 — HasOpenCommsDigitalOutputBrd_1
bit9 — HasOpenCommsDigitalOutputBrd_2
bit10 — HasRemoteStatusPanelBrd_1
bit11 — not used (set to 0)
bit12 — not used (set to 0)
bit13 — not used (set to 0)
bit14 — EnableDialIn
bit15 — EnableDialOut

Comms Options 2

bit0 — EnablePager
bit1 — EnableOCDINormallyClosed
bit2-3 — OCDO1Assignment (0=User Defined, 1=Standard Set or 2=AS400)
bit4-5 — OCDO2Assignment (0=User Defined, 1=Standard Set or 2=AS400)
bit6 through bit15 — not used (set to 0)

Advertising