14.1.6 Electrical Requirements

14.1.7 Surge Suppression

The static transfer switch is equipped with transient voltage surge suppression on each input for

surge suppression. The surge suppression is capable of protecting the static transfer switch from

operating outside of tolerances due to surges as defined by IEC 1000-4-5 (1.2/50uS surge, 2kV CM and

1kV DM) as required under EN 50091-2. Optional surge suppression modules (TVSS) are available

for each input of the STS2/PDU for surge protection of the transformers.

14.1.8 Response Time

A dual level fast/slow transfer threshold is used for under voltage detection to allow the STS2/PDU to

be compatible with UPSs and generators. The voltage thresholds and the slow transfer delay time is

user-adjustable. The fast transfer delay time is less than 4 ms.
The over voltage detection uses a single threshold, with programmable level and delay time. See User

Settings on page 101 for instructions on configuring these settings.

14.1.9 Environmental Requirements

See 3.0 - Locating The STS2/PDU for details concerning environmental requirements for the STS2/

PDU.

14.2 System Components

All STS2/PDU models provide two isolation transformers connected to a solid-state, three-pole dual-

position static transfer switch within one enclosure, with the ability to transfer between two input

sources to a single output.
All STS2/PDUs are configured with an LCD Color Graphical Interface touch screen display for moni-

toring and configuring the unit.

Table 23

Electrical requirements

Item

Requirement

Maximum Continuous Current

250, 400, 600, 800 amps

Load Power Factor Range

0.75 to 1.0, leading or lagging

Load Crest Factor

Up to 3.5

Source Voltage Distortion

Up to 10% THD with notches and ringing transients

Overload Capability

125% for 30 minutes 250A-400A
125% for 10 minutes 600A-800A
150% for 2 minutes
500% for 0.25 sec

Table 24

Unit short circuit withstand capability

Unit Voltage

Unit Amps

Withstand Capability

208-240V

250A

100kA

400-600A

100kA

800A

100kA

380-480V

250A

65kA

400-600A

100kA

800A

65kA

600V

250A

25kA

400-600A

25kA

800A

42kA