Sitescan configuration, Saving your communications configurations, System options – Liebert STS2 User Manual

Page 119: Figure 74 system options, Dual output breaker

Advertising
background image

Touch Screen Display

111

SiteScan Configuration

An RS-422 port on the optional Comms Board provides communications with Liebert’s SiteScan.

SiteScan is Liebert’s system monitoring software that allows you to utilize a PC to monitor the Static

Transfer Switch 2 Power Distribution Unit’s status and check alarms. See 6.3 - Comms Board for

more information on this board.
If the STS2/PDU will be connected to SiteScan:

• Select YES for the SiteScan choice in the Comm Options dialog box to activate the card.

Saving Your Communications Configurations

To save you communications configuration settings:
1. When you have completed the Comm Options configurations, ensure you have selected YES for all

the settings that you want activated.

2. Select SAVE to keep the settings.

Whenever you make modifications to the any of the Comm Options, select SAVE to keep the

changes.

System Options

Most System Options are configured at the factory. However, you may need to set two of the choices

after the unit is installed: Wye Output Transformer and Remote Source Selection.

• Select SYSTEM OPTIONS from the System Settings Menu.

The System Options dialog box is displayed.

• An option is enabled by selecting YES.
• An option is disabled by selecting NO.

Figure 74 System options

Dual Output Breaker

This selection is set at the factory. The choice is set to YES to enable both output breakers (CB3 and

CB3A) when two are installed in the unit. If only one output breaker (CB3) is installed, the setting is

set to NO.

Advertising
This manual is related to the following products: