Figure 68 source setpoints, Table 17 setpoint parameters, Table 17 – Liebert STS2 User Manual

Page 110: Setpoint parameters

Advertising
background image

Touch Screen Display

102

To configure the setpoints for each source:
1. Select SOURCE 1/2 SETPOINTS from the User Settings dialog box. The Source 1/2 Setpoints

dialog is displayed.

Figure 68 Source setpoints

2. Select 1 to configure the settings for Source 1.
3. Configure the settings using the keypad or dialog box that is displayed when you touch a button.

4. Select 2 for Source 2.
5. Configure the settings, as described in step 3.
6. Select SAVE to keep the settings for both sources. The Setpoints dialog is closed and the User

Settings dialog is displayed.

7. Select MANUAL MAX XFER PHASE ANGLE. A keypad is displayed.

This setting configures the maximum allowed phase difference between the sources and applies to

all manual transfers as well as any auto retransfer.
a. Configure this setting with a range of +/- 1-30 degrees. The default setting is +/-15 degrees

and the resolution is 1 deg.

b. Select OK to save the setting. The setting is now displayed in the adjacent field in the User

Settings dialog box.

Table 17

Setpoint parameters

Button

Range

Default

Comments

Fast UV Setting (%)

-10 to -30% of Nominal

voltage rating

-20%

Set in increments of 1%.

Slow UV Setting (%)

-5 to -20%

-10%

Set in increments of 1%.

Slow UV detection delay

1-60 cycles

5 cycles

Units: Line Cycle

OV Setting (%)

+5% to +20%

+10%

Set in increments of 1%.

OV Detection Delay

1-255 cycles

3 cycles

Units: 1/4 Line Cycle

I-PK Xfer Lockout

0 – 3.0 multiplied by

the unit current rating.

2.5 Times Unit

Current Rating

I-peak xfer lockout detection point.

Units: Amps RMS. Select the HI or

LO buttons to configure your setting.