0 maintenance, 1 proper tightening of nuts and bolts, Table 29 torque tightening – Liebert STS2 User Manual

Page 152: Table 30 branch circuit breakers, 2 testing the sts2/pdu, 3 changing the air filter, Aintenance, Proper tightening of nuts and bolts, Testing the sts2/pdu, Changing the air filter

Advertising
background image

Maintenance

144

16.0 M

AINTENANCE

Minimal periodic maintenance of the STS2/PDU is required. As with all electrical distribution compo-

nents, the system should be regularly inspected for electrical connection integrity, signs of excessive

temperatures, dirt accumulation and proper system operation.

16.1 Proper Tightening of Nuts and Bolts

The recommended tightening torque for all nuts and bolts is as shown below, unless otherwise

labeled. All power connections are designed to remain at proper torque throughout the lifetime of the

unit.

16.2 Testing the STS2/PDU

The STS2/PDU includes comprehensive system alarms and fault detection to identify operational

problems. To increase the degree of confidence of proper system operation, periodic transfer tests can

be easily performed. For instructions for changing the preferred source and switching sources, see

10.2 - Manual Transfer / Preferred Source Selection.

16.3 Changing the Air Filter

A standard furnace filter is installed behind the air intake in the front door. The air intake allows air

to circulate to cool the unit. Replace the filter when it becomes dirty and impedes air flow. The fre-

quency of changing or cleaning the filter depends on the location in which the unit is located. The size

of the filter is 1 x 25 x 25 in. (254 x 635 x 635mm).

!

WARNING

Only qualified service personnel should perform maintenance on the STS2/PDU.
Lethal voltages exist inside the unit during normal operation.
The unit is supplied by multiple AC power sources. Disconnect and lock out all power sources

before working inside unit.

Table 29

Torque tightening

Bolt Shaft Size

Grade 5 - Imperial

Grade 8.8 - Metric

Electrical Connections with

Belleville Washers

in-lb

(pound-inch)

N-m

(Newton-meter)

in-lb

(pound-inch)

N-m

(Newton-meter)

10-32

25

3

35

4

1/4-20

53

6

80

9.0

5/16-18

107

12

180

20.4

3/8-16

192

22

240

27.1

1/2-13

428

48

480

54.3

Table 30

Branch circuit breakers

Current Rating

in-lb

(pound-inch)

N-m

(Newton-meter)

Up to 30 Amp

35

4.0

40 to 100 Amp

45

5.1

Advertising
This manual is related to the following products: