4 altitude, Table 3 altitude conversion—feet to meters, Altitude – Liebert STS2 User Manual

Page 14: Recommended derating for high altitude operation, Figure 2, Table 3, Altitude conversion—feet to meters, Max. ambi ent t emperature, Altitude—feet °f (°c)

Advertising
background image

Location Considerations

6

2.4

Altitude

The standard units are designed for full load operation up to 4000 feet (1200m) above sea level. See

Figure 1 for recommended deratings for altitudes greater than 4000 feet (1200m).

Figure 1

Recommended derating for high altitude operation

Operation at full load at a higher altitude can be accommodated in ambient temperatures less than

104°F (40°C) ambient. Figure 2 shows the maximum allowable ambient temperature for full load

operation at altitudes above 4000 feet (1200m).

Figure 2

Maximum ambient temperature for full load operation at higher altitudes

Table 3

Altitude conversion—feet to meters

Feet = Meters

4000 = 1200

7500 = 2286

4500 = 1372

8000 = 2438

5000 = 1524

8500 = 2591

5500 = 1676

9000 = 2743

6000 = 1829

9500 = 2896

6500 = 1981

10000 = 3048

7000 = 2134

100

98

96

94

92

90

88

86

90

00

Rating (%)

10

000

95

00

85

00

80

00

75

00

70

00

65

00

60

00

55

00

50

00

45

00

40

00

0

Max. Ambi

ent T

emperature

104.0 (40)

102.2 (39)

100.4 (38)

98.6 (37)

96.8 (36)

95.0 (35)

93.2 (34)

94.1 (33)

89.6 (32)

87.8 (31)

86.0 (30)

0

4000

4500

5000

5500

6000

6500

7000

7500

8000

8500

9000

9500

10000

Altitude—Feet

°F (°C)