6 remote source selection, 7 key lockout switch, 8 static switch redundant output breaker – Liebert STS2 User Manual

Page 24: 9 inline panelboards, 10 i-line panelboards, 11 subfeed breakers, 12 k-factor transformers, 13 surge suppression system, Remote source selection, Key lockout switch

Advertising
background image

Options

16

6.6

Remote Source Selection

The Remote Source Selection allows the preferred input source to be chosen from a remote location. A

user supplied normally open dry contact allows the user to remotely select a source to be the preferred

source in the same process as the local source transfer selection.
If both the input contacts are closed, the current selected preferred source shall be retained. If the

unit’s preferred source selection and Remote Source Selection are active at the same time,

the STS2/PDU follows the last request for a preferred source change, regardless of whether it was

from the local or Remote Source Selection controls.
See 10.3 - Enabling Remote Source Selection for instructions on enabling the Remote Source

Selection.
See Figures 47 and 48 for the location of the Remote Source Selection option.
See 4.4 - Remote Source Selection Wiring and Figure 56 for information on the control wiring.

6.7

Key Lockout Switch

The key lockout switch activates a software lockout of the touch screen display to prevent manual

transfers and configuration changes. When locked out, the touch screen becomes a read-only display.

A key is needed to do manual transfers or change settings.
The alarm silence button is not disabled when in the lockout position.
The switch is located on the front of the unit next to the display; it is behind the front door but can be

operated without opening the front door. See Figures 20 through 22 for the key lockout switch loca-

tion on each unit.
See 13.2.1 - Security and Figure 65 for instructions on using the key lockout switch.

6.8

Static Switch Redundant Output Breaker

A plug-in, non-automatic circuit breaker is provided which allows redundancy in the static switch out-

put power path. The breaker is connected in parallel with the static switch output plug-in non-auto-

matic circuit breaker.

6.9

Inline Panelboards

An output distribution cabinet with either Square D or General Electric inline panelboards with cop-

per bus to accept bolt-in or plug-in circuit breakers. Each panelboard is individually protected by a

225A, 240V, 3-pole panelboard main circuit breaker.
Each panelboard includes a separate isolated neutral bus bar and a safety-ground bus bar for the neu-

tral and safety-ground connections for at least 42 output circuits.

6.10 I-Line Panelboards

An output distribution cabinet with one vertically mounted Square D I-Line panelboard with copper

bus to accept Square D three phase plug-in circuit breakers. The panelboard shall be totally enclosed

with an accent cover.

6.11 Subfeed Breakers

Breakers for feeding remote panelboard(s) or other loads. Available in ratings of 225A or 400A.

6.12 K-Factor Transformers

K20-rated double-shielded copper isolation transformer specially designed to accommodate highly

nonlinear leads in accordance with UL 1561 (in place of standard isolation transformer).

6.13 Surge Suppression System

A fused and monitored high-energy, 80 kAmp/phase surge suppression system by Control Concepts

connected to each input of the unit for superior surge suppression.

NOTE
Only available on units with inline panelboards. 400A breaker not available on 250A units.

Advertising
This manual is related to the following products: