Table 4 input/output conduit plate specifications, Figure 5, Circuit breakers10 – Liebert STS2 User Manual

Page 18: Figure 6, Breakers, Table 4, Input/output conduit plate specifications, H 6 for ty

Advertising
background image

Power and Control Wiring

10

Figure 5

Typical STS2/PDU, one-line diagram, with inline distribution, dual static switch output circuit
breakers

Figure 6

Typical STS2/PDU, one-line diagram, with I-Line distribution, dual static switch output circuit
breakers

The input and output power wire size should be based on the overcurrent protection device, observing

the NEC and local codes.
The STS2/PDU output power, ground and neutral busbars accommodate a wide range of wire sizes.

The STS2/PDU busbars accommodate standard two-hole lugs.
Table 4

Input/output conduit plate specifications

Rating

Maximum Number

of Conduits

Size, in.

250A

12

2"

8

2-1/2"

6

3" or 3-1/2"

400-600A

6

2"

4

2-1/2" or 3"

800A

6

2-1/2"

5

3" or 3-1/2"

Advertising