0 alarms and faults, 1 event mask, Larms – Liebert STS2 User Manual

Page 90: Aults, Event mask, Alarms and faults, See 11.1 - event mask, R to 11.0 - alarms and faults

Advertising
background image

Alarms and Faults

82

11.0 A

LARMS

AND

F

AULTS

Alarms and faults are events that are triggered when the operation of the Static Transfer Switch 2

Power Distribution Unit falls outside of the defined parameters. These events can also be triggered

by: user actions, such as changing configurations, clearing logs, etc.; failed components such as a fan

failure, an SCR that is open or shorted, etc.; and system status, such as open circuit breakers, load on

alternate source, etc. These events can provide a warning or trigger the system to make a change,

such as switch sources or the recording of a history log.
The STS2/PDU monitoring system detects and annunciates a comprehensive set of fault and alarm

conditions. Faults and alarm messages are can be viewed on the LCD touch screen or via the RS-232

port.
On the LCD touch screen, the events are shown in the Status Display panel in the lower left corner of

the touch screen and written to the Event log. You can touch a message to view a definition of an

event and a tip for troubleshooting. See 13.0 - Touch Screen Display for more information about

the touch screen.
If you are monitoring the system through the RS-232 port, see Table 13 for the commands to view

event logs and alarm and fault lists.
Event actions can be triggered by the settings configured from the Event Masks. See 11.1 - Event

Mask for more information.
Faults — A fault indicates that a component of the STS2/PDU has failed or has been damaged. In the

Event Display, faults are indicated in red.
Alarms — An alarm is an event caused by a significant abnormal system condition. In the Event Dis-

play, alarms are indicated in yellow. The setpoints for many of the alarms are configurable through

the User Settings. Many alarms clear themselves when the condition is resolved. If an alarm event

mask is set to latch, the alarm messages remain active until the alarm condition has been corrected

and the RESET button is pushed. See 11.1 - Event Mask for more information on latching.
When the system is furnished with an optional internal or external modem and a telephone line is

connected to the modem, the system can be programmed to automatically dial out upon occurrence of

any of certain designated alarms. The auto-dial feature can be configured for alarms using the Event

Mask option in the touch screen. See Configuring the Modem on page 105 for instructions on for

setting up your modem.

11.1 Event Mask

The STS2/PDU gathers, processes and reports faults and alarms, collectively referred to below as

events. The Event Mask dialog box allows you to set the system’s response for specific alarms and

faults that are generated.
The following mask types are available for each event:

• Latch — If a latch is enabled for the selected event, that event remains active even if the originat-

ing event condition clears. A latched event may only be cleared by pushing the RESET button.

• Dial Out — If the selected event is triggered, the system automatically calls the specified tele-

phone numbers through the modem. For example, a page could be sent or an event could be sent

to a external terminal, via the modem. See 12.0 - Communication Interfaces for more informa-

tion on configuring communications options.

• Event Log — The selected event is date/time stamped and recorded to the Event Log when the

event is triggered.

• Audible — If the selected event is triggered, an audible beeper or horn is sounded by the

STS2/PDU. The beeper continues while this event is active or latched or until the SILENCE but-

ton is pushed.

See Event Masks on page 100 for instructions on setting the mask type via the touch screen dis-

play. See the 12.1.4 - Setting Event Masks with the Terminal for instructions on configuration

using the RS-232 port.

Advertising
This manual is related to the following products: