Touch Screen Display

99

13.3 Mimic Display

The Mimic display provides a color diagram of the operation of the STS2/PDU. This display imitates

the power flow through the Static Transfer Switch 2 Power Distribution Unit and indicates source

status, breaker status, switch status, source voltage and current readings, output power measure-

ments and active alarm messages. See Figure 62.

13.4 Event Controls

The STS 2 detects events when certain thresholds are passed or certain problems occur. The alarm

controls allow you to acknowledge the existence of these events.

• RESET — All latched events whose conditions have cleared are removed from the Event Display.

Faults and alarms that remain active or are not recoverable are not affected when this button is

selected. This button is also used to perform manual I-Peak resets and manual retransfers.

• SILENCE — turns off the audible alarm (horn or beeper) without resetting the triggering event.

This setting does not permanently turn off the horn. The alarm sounds again when the next event

with an audible alarm setting is triggered.

Active events are shown in the Event Display, whereas cleared events can be reviewed via the Event

Log.

13.5 Event Display

The Event Display lists the condition of the STS2/PDU in real-time. Both nominal system parameters

and alarm messages are displayed in the Event Display. You can touch any message in the Event Dis-

play to display more information in the Display Panel to the left. The selected status is displayed in

bold type.

13.6 Menu Bar

As previously mentioned, the menu bar provides both configuration choices and information. The

choices under the Config and Log menus access additional dialog boxes, while the other menu choices

only show information in the display panel.

13.7 Configuration Menu

When you select the CONFIG (Configuration) menu choice, a pop-up menu is dis-

played with four choices.
•SystemRatings— used to configure frequency, voltage and currents settings for

the STS2/PDU.

• Event Mask — allows you to configure system’s response for events.
• User Settings — allows you to configure operations for the STS2/PDU.
• System Settings — accesses another pop-up menu to configure communication

and system choices and the system ID.

Each of these choices accesses a separate dialog box.

System Ratings

The System Ratings menu is used to set the nominal line fre-

quency, nominal voltage and nominal current at which the system

operates when it is installed. These settings are configured when

the system is initialized at the factory or under maintenance and

should not be changed by the user.