Pdu setpoints, Figure 69 pdu setpoints, Table 18 pdu setpoints – Liebert STS2 User Manual

Page 112: System settings, Table 18

Advertising
background image

Touch Screen Display

104

PDU Setpoints

The PDU Setpoints option allows you to configure the following parameters for the PDU, shown in

Figure 69.

• Load Voltage THD (%)
• Neutral Current (% of nom)
• Ground Current (A)
• Load Bus Overcurrent (% of nom)

Figure 69 PDU setpoints

Table 18 shows the range of valid values, default values and resolution for each parameter.

System Settings

The System Settings choice under the Config menu displays another pop-up menu with three choices:

• Comm Options
• System Options
• System ID

To access the System Settings menu:
1. Select CONFIG from the menu bar.
2. Select SYSTEM SETTINGS from the Config menu.

Table 18

PDU setpoints

Button

Range

Default

Resolution

Load Voltage THD (%)

3.0% to 99.9%

15.0%

0.1

Neutral Current (% of nom)

10% to 200%

95%

1

Ground Current (A)

1.0A to 50.0A

5.0A

0.1

Load Bus Overcurrent (% of nom)

50% to 100%

100%