Event Message Help Text

121

15.0 E

VENT

M

ESSAGE

H

ELP

T

EXT

S1 SCR SHORT

Source 1 SCR Short
One or more of the SCRs for Source 1 has shorted. Transferring between sources has been inhibited.
Contact technical support; in the United States, call 1-800-LIEBERT (1-800-543-2378). Outside the 48 contigu-
ous United States contact Liebert Global Services, if available in your area. For international areas not covered
by Liebert Global Services, the Liebert authorized distributor can provide technical support.
Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the
STS2/PDU system from a terminal, type SH and press RETURN on your keyboard to turn off the audible
alarm.
This event and the system status surrounding it have been written to a History Log if the History Logs were not
already full. This event was also written to the Event Log, if so configured.
The alarm has triggered a message to be sent to the modem, if so configured.

S2 SCR SHORT

Source 2 SCR Short.
One or more of the SCRs for Source 2 has shorted. Transferring between sources has been inhibited.
Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the
STS2/PDU system from a terminal, type SH and press RETURN on your keyboard to turn off the audible
alarm.
This event and the system status surrounding it have been written to a History Log if the History Logs were not
already full. This event was also written to the Event Log, if so configured.
The alarm has triggered a message to be sent to the modem, if so configured.

S1 SCR OPEN

Source 1 SCR Open.
One or more SCRs on Source 1 is open. Transferring between sources has been inhibited.
Contact technical support; in the United States, call 1-800-LIEBERT (1-800-543-2378). Outside the 48 contigu-
ous United States contact Liebert Global Services, if available in your area. For international areas not covered
by Liebert Global Services, the Liebert authorized distributor can provide technical support.
STS2/PDU output has been transferred to Source 2.
Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the
STS2/PDU system from a terminal, type SH and press RETURN on your keyboard to turn off the audible
alarm.
This event and the system status surrounding it have been written to a History Log if the History Logs were not
already full. This event was also written to the Event Log, if so configured.
The alarm has triggered a message to be sent to the modem, if so configured.

Key
ALL CAPS = Event message displayed in the Event Display panel in the lower left corner of the LCD.

Indented text = Help text shown in the Display Panel in the lower right corner of LCD.
BOLD = Commands that are sent through the RS-232 port.