Omega Speaker Systems High Speed Load Cell Interface Card LCIC-WIM-BEN User Manual

Page 74

Advertising
background image

73

E.4.1.4 Stabilization Criterion (Tare & Stop)

At the beginning and at the end of a filling cycle the board waits for the
scale to stabilize in order to read its weight. Hence, some stability criterion
is required. The board requires that all readings within ‘Delta Time’ will be
inside a range whose width is ‘Delta Weight’, both at the beginning (Tare)
and at the end (Stop) of the filling cycle. The waiting for that stabilization
is limited by ‘Timeout’, causing an error situation in case of failure.

Delta Weight
See the description above.

Delta Time
See the description above.

Stabilization Timeout
See the description above.

Impacts
The system copes with impacts and automatically resumes the filling in
case the current weight – after stabilization – is less than the current
setpoint.

E.4.1.5 Lazy Filling

Activate
When checked, the board will identify too slow filling, thus reporting an
error earlier than the ‘Timeout’ check would do.

Advertising